The ABB TU890 (3BSC690075R1) is a compact Module Termination Unit for S800 I/O systems, rated 24 V with 8 channels and 2 A maximum current per I/O channel. Maintenance teams sourcing this passive MTU need a tested spare that connects field wiring and process power without delay.
What this module Does in an S800 I/O System
this module is a passive termination unit that links field wiring and the power supply to the I/O modules. It also carries part of the ModuleBus, distributing it to the I/O module and onward to the next MTU. By shifting outgoing position signals to the next MTU, it generates the correct address for each I/O module in the chain.
This unit uses 27 blue process terminals and gray terminals for field signals and process voltage connections. Mechanical keying prevents insertion of the wrong module, and a latching device secures it to DIN rail. The compact housing measures 64 mm wide including connector, 58 mm deep, and 194 mm high including latch, at 0.17 kg.

Tested-Parts Advantage for This Termination Unit
Factory lead times on S800 I/O accessories can stall a maintenance window. SpareTechHub supplies this module as a tested spare: each unit is inspected and functionally checked before dispatch, then condition clearly graded so you know what arrives. This practical approach gives you faster availability than waiting on factory stock, with a verified part rather than an unknown surplus unit.
this module is used with AI890, AI893, AI895, AO890, AO895, DI890 and DO890 I/O modules, including intrinsic safety applications. Because the MTU is passive, its reliability depends on terminal condition and secure mounting. Our testing covers the connection points and ModuleBus path so the unit is ready for installation.

Installation, Compatibility and Sourcing Checks
Mount this module horizontally on DIN rail and observe the operating temperature range of 0 to +55 °C. For vertical mounting, the maximum ambient is 40 °C. The IP20 protection class suits cabinet installation, and the unit carries CE marking plus ATEX/IECEx Zone 2 certification with interface to Zone 0.
Wire sizes accepted on the process connector are solid 0.2 – 4 mm² and stranded 0.2 – 2.5 mm² (24 – 12 AWG). The power supply connector accepts 0.25 – 2.5 mm² (24 – 14 AWG), with recommended torque of 0.5 – 0.6 Nm on both. Before ordering, confirm your I/O module list matches this module compatibility set above and verify the exact revision you need.
Send the exact part number to SpareTechHub for a tested-unit quote within one business day.