The 140ACI04000 doubles the channel count of the Quantum analog input family to sixteen differential multirange inputs, addressed as 17 input words. Ranges cover 4…20 mA, 0…20 mA and 0…25 mA with resolutions from 4095 to 25000 counts depending on range.
Accuracy is +/- 0.125% of full scale with linearity within +/- 12 uA on 4…20 mA and +/- 6 uA on the other ranges; the single-pole low-pass filter sits at 3 dB / 34 Hz and update time is 15 ms for 2- or 4-wire transmitters. Channel-to-bus isolation is tested at 1780 V AC for 60 s and common-mode rejection exceeds -90 dB at 60 Hz.
Broken-wire detection protects 4…20 mA loops. Signalling mirrors the family layout – bus active, external fault, and sixteen green/red channel pairs. The module requires 360 mA of bus current, dissipates 5 W, weighs 0.3 kg and carries UL 508, CSA, FM Class 1 Division 2, cUL and CE approvals.