The 560PSU02 is a power supply unit from ABB. The details below are drawn from the original manufacturer data and describe the real configuration, ratings, and function of this unit.
Application
The power supply unit 560PSU02 generates the two supplyvolt-ages (5 V DC and 24 V DC) for the RTU560 subracks 560MPR03and 560SFR02. The output power is sufficient to supply a sub-rack with up to 8 communication units (CMU).
It is possible to configure redundant power supplies for projectconfigurations with higher requirements to availability. In this con-figuration two power supply units 56OPSU02 are operating inparallel mode. They are able to take over the full load, if one pow-er supply fails. Only power supplies of the same type and rubricshould be used for redundant operation.
The input voltage of the power supply unit is 48… 220 V DC.
Characteristics
The power supply unit 560PSU02 has the following character-istics and functions:
一
–
Potential isolation between the input and the outputsCodling by natural convection
Electronic power limitation on outputs
Short-circuit proof outputs
Over-voltage protection of the inputReverse voltage protection of the inputParalel operation with monitoring of redundant power sup-
ply configuration
Contrdlled load balancing in redundant operationLEDs for monitoring the output voltagesAlarm indication in case of failure
Tolerant oninput voltage interuptions up to 50 ms
Input
Input voltage:
Input tolerance range
Voltage Interruption
Max. input current
Starting Current:
48…220 V DC
20%… +15%
$ 50 ms; 0% UN (UN2 48V)
2.4… 0.5A
< 10A; 50us -1.5ms
(Class S1 according to IEC 60870-4)
Fuse
Efficiency:
External circuit-breaker
F1=4AT
74% @ 48…110 VDC
The plus lead needs a be protected bya circuit-breaker upstream with 10 A
trip current.
Reverse voltage protection
yes
Output
Total output power
Derating
85W
-2,5 %/Kelvin; 50°C
Output U1
Voltage
Tolerance
Current min.
Current max
Residual Ripple
5.1VDC
5.0…5.3VDC
0A
15A
s 30 mVss
Output U2
Voltage
Tolerance
24 VDC
22,4 …26,3 VDC
Current min.
Current max.
Residual Ripple
0A
0,4A
s 80 mVss
Mechanical layout
Dimensions
160 mm x 100 mm, 3HE euro card
format
8R (40 mm) front panel
Housing type
Mounting
Weight
Printed circuit board
for mounting in RTU560 racks
ca. 0,65 kg
Connection type
RTU560 backplanecannector
Supply connector
48pdetypeF DN 41612
3 pole 7.62 mm pluggable screw ter-minals (included in delivery)0.2… 2.5 mm2/AWG 24 – AWG 12
Environmentalconditions
Nominal operating temperature range:0°C… 70%C
EN 60068-2-1,-2-2,-2-14
Relative humidity
EN60068-2-30
5…95 9
(non condensing)
Ordering information
560PSU02 R0001
1KGT011900R0001