The ATV610U40N4Z is an Altivar 610 variable speed drive from Schneider Electric’s Easy Altivar 610 line, rated 4 kW (5 HP) normal duty for pumps and fans. It operates from a 380…460 V three-phase supply and carries a built-in Category C3 EMC filter. This version ships without a display terminal; the optional VW3A1113 text keypad connects through the RJ45 HMI port.
Motor control supports the U/f Vc Standard mode.
Serial communication is built in over Modbus RTU through 2 RJ45 ports. The output frequency range covers 0.1…500 Hz.
SpareTechHub supplies the ATV610U40N4Z as refurbished, tested surplus stock. Request a quote for current pricing, availability and lead time.
Key specifications
| Product type | Variable speed drive (AC frequency inverter) |
|---|---|
| Motor compatibility | Three-phase asynchronous and synchronous motors (open loop) |
| Control mode | U/f Vc Standard (STD), U/f Vc 5-point (UF5), U/f Vc Quadratic (UFQ, for variable-torque fan/pump), open-loop synchronous motor control (SYNU, for PMSM), and reluctance motor control (SRVC) (per programming manual EAV64387 p.72–73) |
| Rated motor power | 4 kW (5 HP) normal duty; 3 kW heavy duty |
| Frame size | 1 |
| Integrated HMI | None (plain text display terminal not supplied with this version; VW3A1113 keypad can be connected via the RJ45 HMI port as an accessory) |
| Integrated EMC filter | Category C3 EMC filter |
| Supply voltage | 380…460 V AC, 50/60 Hz, three-phase |
| Maximum continuous output current | 9.3 A (normal duty) |
| Output frequency | 0.1…500 Hz |
| Switching frequency | 2…12 kHz adjustable; 4 kHz nominal (derate above nominal per Installation Manual) |
| Braking | external braking-chopper resistor terminals (PA/+, PB) provided for connection of an external braking resistor; no integrated braking-transistor current rating or braking-torque figure is published in the official catalog/installation manual (deferred to programming manual) |
| Analog inputs | 3, software-configurable 0…10 V / 0…20 mA (voltage, current, temperature probe, or water level sensor) |
| Digital inputs | 6, 24 V DC (2 can be programmed as pulse inputs) |
| Relay outputs | 3, configurable relay logic |
| Protocols | Modbus RTU (Modbus serial link) |
| Operating temperature | -15…+45 °C without derating; up to +60 °C with power derating |
| Protection rating | IP20 (IP40 on the top of the product) |