Specifications

Technical Details

Device classification Bus coupler / distributed I/O slave (not a programmable controller)
Digital inputs 12 (24 Vdc, sink/source, Type 1 per IEC 61131-2)
Digital outputs 8 (2 solid-state PNP 0.3 A + 6 relay 2 A)
Analog inputs None
Analog outputs None
High-speed counters 2 × 20 kHz
Pulse outputs 2 × 7 kHz pulse generator
Expansion modules (max) Up to 7 TM2 expansion modules
Built-in ports 1× CANopen (SUB-D9)
Protocols CANopen (slave)
Communication expansion Defined by NIM (Network Interface Module) variant; this NIM = CANopen; no further comms expansion
Supply voltage 24 V DC (20.4...26.4 V)
Power consumption 19 W
Bus current 700 mA at 26.2 V (supply circuit)

Overview

OTB1C0DM9LP
I/O distributed module OTB – CANopen bus –
0..1000 m

Main
Range of product Modicon OTB
Product or component type I/O distributed module
Integrated connection type CANopen bus SUB-D 9, transmission mode: 2 twisted shielded pairsat 10 kbit/s…1 Mbit/s
Bus type CANopen S20, profile: DS 401 V2.1, method of access: CSMA/MA multimaster with priority
conforming to DR303-2
CANopen S20, profile: DS 401 V2.1, method of access: CSMA/MA multimaster with priority
conforming to DS301 V4.02
Discrete input number 12 conforming to EN/IEC 61131 type 1
Discrete input logic Sink or source
Discrete input current 5 mA for I0…I1
5 mA for I6…I7
7 mA for I2…I5
7 mA for I8…I11
Discrete output number 2 solid state PNP for Q0…Q1 output logic: source
6 relay for Q2…Q7
Discrete output current 2000 mA relay
300 mA solid state
Complementary
Topology Devices linked by daisy-chaining or tap junctions
Number of slave 0…63
Bus length 0…100 m tap-off length: 0…10 m, 500 kbit/s
0…1000 m tap-off length: 0…120 m, 50 kbit/s
0…250 m tap-off length: 0…10 m, 250 kbit/s
0…2500 m tap-off length: 0…300 m, 20 kbit/s
0…40 m tap-off length: 0…6 m, 800 kbit/s
0…500 m tap-off length: 0…10 m, 125 kbit/s
0…5000 m tap-off length: 0…600 m, 10 kbit/s
0…20 m, 1 Mbit/s
Number of devices per segment 0…16, length of segment 0…205 m
0…32, length of segment 0…185 m
0…64, length of segment 0…160 m

Discrete input voltage 24 V
Discrete input voltage type DC
Discrete input type NPN or PNP
Input voltage limits 20.4…26.4 V
Electronic filtering time 0.035 ms for I0…I1 at state 1
0.035 ms for I6…I7 at state 1
0.04 ms for I2…I5 at state 1
0.04 ms for I8…I11 at state 1
0.045 ms for I0…I1 at state 0
0.045 ms for I6…I7 at state 0
0.15 ms for I2…I5 at state 0
0.15 ms for I8…I11 at state 0
Configurable filtering time 0 ms
12 ms
3 ms
Input impedance 3.4 kOhm for I2…I5
3.4 kOhm for I8…I11
5.7 kOhm for I0…I1
5.7 kOhm for I6…I7
Discrete output voltage 24 V DC solid state
240 V AC relay
30 V DC relay
Output voltage limits 20.4…28.8 V solid state
Output current limits 360 mA solid state
Current per output common 8 A relay
<= 0.72 A solid state
Current consumption 30 mA at 5 V DC (at state 1) relay output
40 mA at 24 V DC (at state 1) relay output
5 mA at 5 V DC (at state 0) relay output
Output overvoltage protection 38…40 V
Tungsten load 8 W for solid state
Response time 300 µs at state 0 for relay
300 µs at state 1 for relay
5 µs at state 0 for solid state
5 µs at state 1 for solid state
Switchable load >= 0.1 mA
Contact bounce time <= 1 ms for relay
Leakage current <= 0.1 mA at state 0 for solid state
Drop-out voltage <= 1 V at state 1
Insulation between channels and
internal logic
1500 Vrms for 1 minute for relay output
500 Vrms for 1 minute for input circuit
500 Vrms for 1 minute for solid state output
Insulation between channels None
Contact resistance <= 30 mOhm
Electrical durability 500000 cycles AC-1 with 500 VA load for relay output
500000 cycles AC-14 with 250 VA load for relay output
500000 cycles AC-15 with 200 VA load for relay output
500000 cycles DC-1 with 60 W load for relay output
500000 cycles DC-13 with 30 W load for relay output
Supply circuit type DC
[Us] rated supply voltage 24 V
Supply voltage limits 20.4…26.2 V
Input current <= 700 mA at 26.2 V for supply circuit
Inrush current <= 1 A for solid state output
<= 50 A for supply circuit
Power consumption 19 W
Number of I/O expansion module 0…7
I/O expansion capacity 132 with screw terminal discrete I/O module(s)
188 with spring terminal discrete I/O module(s)
244 with HE10 connector discrete I/O module(s)
7 x 8I or 7 x 2I or 7 x (4I/2O) with screw terminal analogue I/O module(s)
Insulation resistance >= 10 mOhm between I/O and earth terminals

>= 10 mOhm between power supply and earth
I/O connection Removable screw terminal block
Number of common point 1 for relay output (1 NO)
1 for relay output (2 NO)
1 for relay output (3 NO)
1 for input
1 for solid state output
Counting input number 2
Counting capacity 32 bits
Counting frequency 20000 Hz
5000 Hz
Pulse generator number 2
Pulse generator frequency 7 kHz
Pulse generator function RPLS pulse generator output
RPWM pulse width modulation
Marking CE
Fixing mode By clips on 35 mm symmetrical DIN rail
By screws on panel with fixing kit
By screws on solid plate with fixing kit
Status LED 1 LED per channel, green for I/O
1 LED, green for PWR
1 LED, green for RUN
1 LED, red for ERR
Product weight 0.195 kg
Environment
IP degree of protection IP20
Immunity to microbreaks 10 ms for supply circuit
Dielectric strength 500 V between I/O and earth terminals
500 V between power supply and earth
Standards CSA
EN 61131-2
IEC 61131-2
UL 508
CSA C22.2 No 213 Class I Division 2 Group A
CSA C22.2 No 213 Class I Division 2 Group B
CSA C22.2 No 213 Class I Division 2 Group C
CSA C22.2 No 213 Class I Division 2 Group D
Product certifications CULus
Ambient air temperature for operation 0…55 °C
Ambient air temperature for storage -25…70 °C
Relative humidity 30…95 % without condensation
Pollution degree 2 conforming to EN 60664
2 conforming to IEC 60664
Operating altitude 0…2000 m
Storage altitude 0…3000 m
Vibration resistance 0.075 mm (f = 10…57 Hz) on 35 mm symmetrical DIN rail
1 gn (f = 57…150 Hz) on 35 mm symmetrical DIN rail
Shock resistance 15 gn for 11 ms conforming to EN 61131
15 gn for 11 ms conforming to IEC 61131
Resistance to electrostatic discharge 4 kV in contact conforming to IEC 61000-4-2
8 kV in air conforming to EN 61000-4-2
8 kV in air conforming to IEC 61000-4-2
4 kV in contact conforming to EN 61000-4-2
Resistance to radiated fields 10 V/m, 80000000…2000000000 Hz conforming to EN 61000-4-3
10 V/m, 80000000…2000000000 Hz conforming to IEC 61000-4-3
Resistance to fast transients 1 kV for 24 V solid state I/O conforming to IEC 61000-4-4
2 kV for 24 V supply conforming to IEC 61000-4-4

Key specifications

  • Device classification: Bus coupler / distributed I/O slave (not a programmable controller)
  • Digital inputs: 12 (24 Vdc, sink/source, Type 1 per IEC 61131-2)
  • Digital outputs: 8 (2 solid-state PNP 0.3 A + 6 relay 2 A)
  • Analog inputs: None
  • Analog outputs: None
  • High-speed counters: 2 × 20 kHz
  • Pulse outputs: 2 × 7 kHz pulse generator
  • Expansion modules (max): Up to 7 TM2 expansion modules
  • Built-in ports: 1× CANopen (SUB-D9)
  • Protocols: CANopen (slave)
  • Communication expansion: Defined by NIM (Network Interface Module) variant; this NIM = CANopen; no further comms expansion
  • Supply voltage: 24 V DC (20.4…26.4 V)
  • Power consumption: 19 W
  • Bus current: 700 mA at 26.2 V (supply circuit)
Common questions

Frequently Asked Questions

What is the part number of this product?

The part number is OTB1C0DM9LP, manufactured by Schneider Electric. The marking on the unit itself should match this number — confirm the revision code on the nameplate when comparing with your installed hardware.

What condition is this OTB1C0DM9LP shipped in?

This unit is offered as refurbished / tested stock: inspected and condition-graded before shipping, packed in protective anti-static material. The current availability and condition grade are confirmed in your quote.

How do I get a quote for OTB1C0DM9LP?

Use the Request a Quote button on this page or send us your model list — pricing, lead time and warranty terms are returned within one business day. A service manual download is available above when applicable.

What are the key specifications of OTB1C0DM9LP?

OTB1C0DM9LP is specified as Device classification: Bus coupler / distributed I/O slave (not a programmable controller); Digital inputs: 12 (24 Vdc, sink/source, Type 1 per IEC 61131-2); Digital outputs: 8 (2 solid-state PNP 0.3 A + 6 relay 2 A). The full set of verified technical parameters is listed in the specification table above.

Need this part?

Get pricing, condition and lead time in one business day.