Skip to content

Fast quotes for industrial automation spare parts — send your model list today.

Schneider Electric

TM3DQ8R | Schneider Electric Discrete output module

Schneider Electric TM3DQ8R Modicon TM3 - 8 relay outputs (screw) 24Vdc

Part Number TM3DQ8R

Refurbished / Tested

Also known as: TM3DQ8R · Schneider Electric TM3DQ8R · TM3DQ8R | Schneider Electric Discrete output module

  • Inspected and condition-graded before shipping
  • Quote with lead time and warranty in 1 business day
  • Global shipping with protective packaging
Specifications

Technical Details

Module type Digital output (relay)
Channels 8
Signal type Relay output, NO (normally open)
Range 5-30 Vdc / 5-250 Vac (max)
Output current 2 A per channel (max), 7 A per common line
Resolution N/A
Accuracy N/A
Isolation 500 V AC between output and internal logic; 1500 V AC between channel groups
Diagnostics Module status, bus status
Response time Mechanical relay
Wiring Removable screw terminal block, 5.08 mm pitch
Supply voltage 24 Vdc (via TM3 bus)
Power consumption Not available
Bus current 30 mA at 5 V DC (all outputs on); 5 mA (all outputs off)

Overview

Schneider Electric TM3DQ8R
Modicon TM3 – 8 relay outputs (screw) 24Vdc

Main
Range of product Modicon TM3
Product or component
type
Discrete output module
Range compatibility Modicon M241
Modicon M251
Modicon M221
Modicon M262
Discrete output type Relay normally open
Discrete output number 8
Discrete output logic Positive or negative
Discrete output voltage 24 V DC for relay output
240 V AC
Discrete output current 2000 mA for relay output

Complementary
Discrete I/O number 8
Current consumption 5 mA at 5 V DC via bus connector (at state off)
0 mA at 24 V DC via bus connector (at state off)
40 mA at 24 V DC via bus connector (at state on)
30 mA at 5 V DC via bus connector (at state on)
Response time 10 ms (turn-on)
5 ms (turn-off)
Mechanical durability 20000000 cycles
Minimum load 10 mA at 5 V DC for relay output
Local signalling 1 LED per channel (green) for output status
Electrical connection 11 x 2.5 mm² removable screw terminal block with pitch 5.08 mm adjustment for
outputs
Maximum cable distance between devices Unshielded cable: <30 m for relay output
Insulation Between output and internal logic at 2300 V AC
Between outputs at 750 V AC
Between output groups at 1500 V AC
Marking CE
Mounting support Top hat type TH35-15 rail conforming to IEC 60715
Top hat type TH35-7.5 rail conforming to IEC 60715
Plate or panel with fixing kit
Height 90 mm
Depth 84.6 mm
Width 27.4 mm
Net weight 0.11 kg
Environment
Standards EN/IEC 61131-2
Product certifications CE[RETURN]cULus[RETURN]UKCA[RETURN]RCM[RETURN]EAC[RETURN]cULus
HazLoc
Resistance to electrostatic discharge 8 KV in air conforming to EN/IEC 61000-4-2
4 kV on contact conforming to EN/IEC 61000-4-2
Resistance to electromagnetic fields 10 V/M 80 MHz…1 GHz conforming to EN/IEC 61000-4-3
3 V/M 1.4 GHz…2 GHz conforming to EN/IEC 61000-4-3
1 V/m 2 GHz…3 GHz conforming to EN/IEC 61000-4-3
Resistance to magnetic fields 30 A/m 50/60 Hz conforming to EN/IEC 61000-4-8
Resistance to fast transients 2 kV for relay output conforming to EN/IEC 61000-4-4
Surge withstand 1 kV I/O common mode conforming to EN/IEC 61000-4-5 DC

Resistance to conducted disturbances 10 V 0.15…80 MHz conforming to EN/IEC 61000-4-6
3 V spot frequency (2, 3, 4, 6.2, 8.2, 12.6, 16.5, 18.8, 22, 25 MHz) conforming to
Marine specification (LR, ABS, DNV, GL)
Electromagnetic emission Radiated emissions – test level: 40 dBμV/m QP class A ( 10 m) at 30…230 MHz
conforming to EN/IEC 55011
Radiated emissions – test level: 47 dBμV/m QP class A ( 10 m) at 230…1000 MHz
conforming to EN/IEC 55011
Ambient air temperature for operation -10…35 °C vertical installation
-10…55 °C horizontal installation
Ambient air temperature for storage -25…70 °C
Relative humidity 10…95 %, without condensation (in operation)
10…95 %, without condensation (in storage)
IP degree of protection IP20 with protective cover in place
Pollution degree 2
Operating altitude 0…2000 m
Storage altitude 0…3000 m
Vibration resistance 3.5 mm at 5…8.4 Hz on DIN rail
3 gn at 8.4…150 Hz on DIN rail
3.5 mm at 5…8.4 Hz on panel
3 gn at 8.4…150 Hz on panel
Shock resistance 15 gn for 11 ms
Packing Units
Unit Type of Package 1 PCE
Number of Units in Package 1 1
Package 1 Height 7.519 cm
Package 1 Width 10.487 cm
Package 1 Length 12.849 cm
Package 1 Weight 240.0 g

Key specifications

  • Module type: Digital output (relay)
  • Channels: 8
  • Signal type: Relay output, NO (normally open)
  • Range: 5-30 Vdc / 5-250 Vac (max)
  • Output current: 2 A per channel (max), 7 A per common line
  • Resolution: N/A
  • Accuracy: N/A
  • Isolation: 500 V AC between output and internal logic; 1500 V AC between channel groups
  • Diagnostics: Module status, bus status
  • Response time: Mechanical relay
  • Wiring: Removable screw terminal block, 5.08 mm pitch
  • Supply voltage: 24 Vdc (via TM3 bus)
  • Power consumption: Not available
  • Bus current: 30 mA at 5 V DC (all outputs on); 5 mA (all outputs off)
Common questions

Frequently Asked Questions

What is the part number of this product?

The part number is TM3DQ8R, manufactured by Schneider Electric. The marking on the unit itself should match this number — confirm the revision code on the nameplate when comparing with your installed hardware.

What condition is this TM3DQ8R shipped in?

This unit is offered as refurbished / tested stock: inspected and condition-graded before shipping, packed in protective anti-static material. The current availability and condition grade are confirmed in your quote.

How do I get a quote for TM3DQ8R?

Use the Request a Quote button on this page or send us your model list — pricing, lead time and warranty terms are returned within one business day. A service manual download is available above when applicable.

What are the key specifications of TM3DQ8R?

TM3DQ8R is specified as Module type: Digital output (relay); Channels: 8; Signal type: Relay output, NO (normally open). The full set of verified technical parameters is listed in the specification table above.

Need this part?

Get pricing, condition and lead time in one business day.