Modicon TM3 – 4 analog /
temperature inputs (screw) 24Vdc
Main
Range of product Modicon TM3
Product or component type Analog input module
Range compatibility Modicon M221
Modicon M241
Modicon M251
Modicon M262
Analogue input number 4
Analogue input type current 4…20 mA
current 0…20 mA
voltage 0…10 V
voltage – 10…10 V
thermocouple – 200…1000 °C with thermocouple J
thermocouple – 200…1300 °C with thermocouple K
thermocouple 0…1760 °C with thermocouple R
thermocouple 0…1760 °C with thermocouple S
thermocouple 0…1820 °C with thermocouple B
thermocouple – 200…400 °C with thermocouple T
thermocouple – 200…1300 °C with thermocouple N
thermocouple – 200…800 °C with thermocouple E
thermocouple 0…2315 °C with thermocouple C
Ni 100/Ni 1000 temperature probe – 60…180 °C
Pt 100 temperature probe – 200…850 °C
Pt 1000 temperature probe – 200…600 °C
Complementary
Analogue input resolution 16 bits
15 bits + sign
Permissible continuous overload 13 V, analogue input type: voltage
40 mA, analogue input type: current
Input impedance <= 50 Ohm current
>= 1 MOhm voltage
>= 1 MOhm thermocouple
>= 1 MOhm temperature probe
LSB value 2.44 mV 0…10 Vvoltage
4.88 mV – 10…10 Vvoltage
4.88 µA 0…20 mAcurrent
3.91 µA 4…20 mAcurrent
0.1 °Ctemperature probe
0.1 °Cthermocouple
Conversion time 100 ms + 100 ms per channel + 1 controller cycle time for analogue input
thermocouple
100 ms + 100 ms per channel + 1 controller cycle time for analogue input
temperature probe
10 ms + 10 ms per channel + 1 controller cycle time for analogue input voltage/
current
Sampling duration 10 ms, analogue input type: voltage/current
100 ms, analogue input type: voltage/current
100 ms, analogue input type: thermocouple
100 ms, analogue input type: temperature probe
Absolute accuracy error +/- 0.2 % of full scale at 25 °C for analogue input voltage/current
+/- 0.2 % of full scale at 25 °C for Pt 100/Pt 1000, Ni 100/ Ni 1000 temperature probe
+/- 0.2 % of full scale at 25 °C for thermocouple C 0…2315 °C
+/- 6 °C at 25 °C for thermocouple R, S 0…200 °C
+/- 0.2 % of full scale at 25 °C for thermocouple R, S 200…1760 °C
+/- 0.2 % of full scale at 25 °C for thermocouple B 300…1820 °C
+/- 0.4 % of full scale at 25 °C for thermocouple K – 200…0 °C
+/- 0.2 % of full scale at 25 °C for thermocouple K 0…1300 °C
+/- 0.4 % of full scale at 25 °C for thermocouple J – 200…0 °C
+/- 0.2 % of full scale at 25 °C for thermocouple J 0…1000 °C
+/- 0.4 % of full scale at 25 °C for thermocouple E – 200…0 °C
+/- 0.2 % of full scale at 25 °C for thermocouple E 0…800 °C
+/- 0.4 % of full scale at 25 °C for thermocouple T – 200…0 °C
+/- 0.2 % of full scale at 25 °C for thermocouple T 0…400 °C
+/- 0.4 % of full scale at 25 °C for thermocouple N – 200…0 °C
+/- 0.2 % of full scale at 25 °C for thermocouple N 0…1300 °C
Temperature drift +/- 0.01 %FS/°C
Repeat accuracy +/-0.5 %FS
Non-linearity +/- 0.2 %FS
Cross talk <= 1 LSB
[Us] rated supply voltage 24 V DC
Supply voltage limits 20.4…28.8 V
Type of cable Twisted shielded pairs cable <30 m for input circuit
Current consumption 45 mA at 5 V DC via bus connector
50 mA at 5 V DC via bus connector
35 mA at 24 V DC via external supply
40 mA at 24 V DC via external supply
Local signalling 1 LED (green) for PWR
Electrical connection 10 x 1.5 mm² removable screw terminal block with pitch 3.81 mm adjustment for
inputs and supply
10 x 1.5 mm² removable screw terminal block with pitch 3.81 mm adjustment for
inputs
Insulation Between input and supply at 1500 V AC
Between input and internal logic at 500 V AC
Marking CE
Surge withstand 1 kV power supply common mode conforming to IEC 61000-4-5
0.5 kV power supply differential mode conforming to IEC 61000-4-5
1 kV input common mode conforming to IEC 61000-4-5
Mounting support Top hat type TH35-15 rail conforming to IEC 60715
Top hat type TH35-7.5 rail conforming to IEC 60715
plate or panel with fixing kit
Height 90 mm
Depth 70 mm
Width 23.6 mm
Net weight 0.11 kg
Environment
Standards IEC 61131-2
Product certifications CE
UKCA
RCM
EAC
cULus
cULus HazLoc
Resistance to electrostatic
discharge
8 kV in air conforming to IEC 61000-4-2
4 kV on contact conforming to IEC 61000-4-2
Resistance to electromagnetic
fields
10 V/m 80 MHz…1 GHz conforming to IEC 61000-4-3
3 V/m 1.4 GHz…2 GHz conforming to IEC 61000-4-3
1 V/m 2 GHz…3 GHz conforming to IEC 61000-4-3
Resistance to magnetic fields 30 A/m conforming to IEC 61000-4-8
Resistance to fast transients 1 kV (I/O) conforming to IEC 61000-4-4
Resistance to conducted
disturbances
10 V 0.15…80 MHz conforming to IEC 61000-4-6
3 V spot frequency (2, 3, 4, 6.2, 8.2, 12.6, 16.5, 18.8, 22, 25 MHz) conforming to
Marine specification (LR, ABS, DNV, GL)
Electromagnetic emission Radiated emissions – test level: 40 dBμV/m QP class A ( 10 m) at 30…230 MHz
conforming to IEC 55011
Radiated emissions – test level: 47 dBμV/m QP class A ( 10 m) at 230…1000 MHz
conforming to IEC 55011
Immunity to microbreaks 10 ms
Ambient air temperature for
operation
-10…55 °C horizontal installation
-10…35 °C vertical installation
Ambient air temperature for
storage
-25…70 °C
Relative humidity 10…95 %, without condensation (in operation)
10…95 %, without condensation (in storage)
IP degree of protection IP20
pollution degree 2
Operating altitude 0…2000 m
Storage altitude 0…3000 m
Vibration resistance 3.5 mm at 5…8.4 Hz on DIN rail
3 gn at 8.4…150 Hz on DIN rail
Shock resistance 15 gn for 11 ms
Packing Units
Unit Type of Package 1 PCE
Number of Units in Package 1 1
Package 1 Height 7.500 cm
Package 1 Width 10.500 cm
Package 1 Length 12.500 cm
Package 1 Weight 215.000 g
Key specifications
- Module type: Analog input (temperature: thermocouple/RTD/mV/voltage/current)
- Channels: 4
- Signal type: Thermocouple (J, K, T, E, N, S, R, B), RTD (PT100, PT1000, NI100, NI1000, CU100), 0-10 Vdc, ±10 Vdc, 0-20 mA, 4-20 mA (software configurable per channel)
- Range: Per sensor type (e.g., PT100: -200…+850 °C; Type K: -270…+1372 °C)
- Resolution: 16 bits (15 bits + sign)
- Accuracy: ±0.2% of full scale at 25 °C (voltage/current/RTD); ±0.4…±0.2% FS for thermocouple depending on type
- Isolation: 1500 V AC between input and supply; 500 V AC between input and internal logic
- Diagnostics: Channel status (sensor break, short circuit), module status, bus status
- Response time: Conversion: 100 ms + 100 ms per channel + 1 controller cycle time (thermocouple); 10 ms per channel sampling
- Wiring: Removable screw terminal block, 3.81 mm pitch
- Supply voltage: 24 Vdc (via TM3 bus)
- Power consumption: Not available
- Bus current: 45 mA at 5 V DC; 35 mA at 24 V DC
- Operating temperature: 0…+55 °C