Bently Nevada 350900: 482 °C at the Head, 125 °C at the Board

Large turbine-generator set inside a power plant hall, the casing measurement environment for a Bently Nevada 350900 HTVAS sensor

The Bently Nevada 350900 High Temperature Velocity and Acceleration Sensor (HTVAS) splits the measurement chain in three: a sensing head rated to +482 °C (+900 °F), a mineral-insulated integral cable rated to the same +482 °C, and signal-conditioning electronics rated to +125 °C (+257 °F) and survivable to +155 °C for four hours. It is not a single probe that tolerates 482 °C end to end. The datasheet (168780 Rev. L) also confirms that velocity and acceleration are delivered as two simultaneous outputs from one sensing head — the velocity channel is generated inside the integral electronics, not by an external integrator — and that the two signals must be wired to a separate channel pair on a 3500/42M or 3500/44M monitor.

Three claims that circulate with this sensor are worth correcting at the start. The 482 °C figure applies to the sensor and its mineral-insulated cable, not to the electronics housing or its MIL-DTL-83723/90 connector. The velocity output is not derived by a separate signal-conditioning unit in the cabinet; both outputs leave the same permanently connected assembly. And the published sensitivities are 10 mV/g and 100 mV/in/s — the marketing figures and this datasheet agree, which is not always the case in this product family.

TL;DR

  • Temperature split: sensing head −54 °C to +482 °C; mineral-insulated cable −54 °C to +482 °C; integral electronics −54 °C to +125 °C, with a four-hour survival rating at +155 °C during which electrical performance is not guaranteed.
  • Two outputs, one sensing head: acceleration 1.02 mV/m/s² (10 mV/g) ±5% and velocity 3.94 mV/mm/s (100 mV/in/s) ±5%, both continuous. The datasheet requires the pair to be used on separate channels (for example channels 1 and 3) or separate monitors.
  • Accuracy over temperature: both channels stay within ±10% of nominal with the sensor at −54 °C to +399 °C, and within ±15% at the full +482 °C rating.
  • Ranges: 4,900 m/s² (500 g) acceleration, 1,270 mm/s (50 in/s) velocity, ±1% amplitude linearity to 500 g peak, mounted resonance above 15 kHz.
  • Power: −18 to −30 Vdc, 6 mA nominal quiescent, case isolated. Hazardous-area versions are limited to −18 to −28 Vdc and must be fed from a limited-energy or Class 2 supply.
  • Cable: 300-series stainless mineral-insulated integral cable with stainless overbraid, 6.35 ± 1.27 mm diameter, 51 mm minimum bend radius, 305 m (1,000 ft) maximum total length.
  • Certifications exist and are specific: ATEX/IECEx II 1 G Ex ia IIC/IIB and II 3 G Ex ec, cNRTLus Class I Div 1 and Div 2, ABS marine. The 482 °C ambient limit appears in the ATEX conditions of safe use for the sensor and cable only.

Where does the 482 °C rating actually stop on the 350900?

The ruling applies to two of the three assemblies, and the third has its own limit that is often left out of the datasheet summary. Bently Nevada rates the sensor −54 °C to +482 °C, rates the mineral-insulated cable over the identical range, and rates the integral signal-conditioning electronics at −54 °C to +125 °C, with a four-hour survival exposure to +155 °C during which electrical performance does not have to be met. The sensor head and the cable are therefore the only parts that may sit on a 482 °C surface. The electronics must be relocated to a cooler location, which is the entire reason the product is split into two bodies joined by a hardline cable.

The hazardous-area conditions of safe use make the same split explicit in ambient-temperature terms:

Assembly Operating temperature (general specification) ATEX/IECEx ambient limit Can it sit at 482 °C?
Sensing head −54 °C to +482 °C −40 °C to +482 °C Yes
Mineral-insulated integral cable −54 °C to +482 °C −40 °C to +482 °C Yes
Integral signal-conditioning electronics −54 °C to +125 °C −40 °C to +100 °C (T4) No
MIL-DTL-83723/90 connector Part of the electronics housing −40 °C to +100 °C (T4) No

Two practical consequences follow. First, a 482 °C installation is a two-location installation: the head goes on the hot surface, the electronics go where ambient stays under 100 °C in a hazardous area, or under 125 °C in a general-purpose area. Second, the connector is on the electronics, so no part of the high-temperature zone depends on a connector surviving heat. Bently Nevada states that removing the connection between the sensing head and its electronics removes “a significant source of potential transducer failures (connector problems).”

Does the 350900 output velocity and acceleration from one sensing head?

Yes, and both outputs are continuous. The datasheet describes “a continuous acceleration and velocity output” that lets a plant protect the machine on velocity while simultaneously capturing acceleration for diagnostics. The velocity signal is produced by the integral signal-conditioning electronics that are permanently hardwired to the sensing head, so there is no separate integrator or charge amplifier in the cabinet. What the user must provide is not signal conditioning but two destinations: the acceleration and velocity signals have to be wired to a separate channel pair on a 3500/42M or 3500/44M, or to separate monitors.

That channel-pair rule is the most common commissioning mistake. A 3500/42M channel is configured for one measurement type; putting both outputs into one channel pair is not a valid configuration. Bently Nevada’s own wording is “such as channels 1 and 3”, which means two channels on the same monitor are acceptable as long as they are not the same pair.

Physically the assembly is three parts: the sensing head (nickel alloy 600, 30.2 mm square four-hole mounting pattern, 7.2 mm holes, 32 microinch rms mounting surface), the mineral-insulated cable, and the electronics housing (300-series stainless, patch-panel hub mount) terminated in a MIL-DTL-83723/90-1006N connector with gold-plated 300-series stainless contacts. The order code 350900-AAA selects only the integral cable length; the field interconnect cable is a separate part, 350901-AAA, in 10 ft or 40 ft.

What sensitivity, range and frequency response does the datasheet publish?

The published sensitivities are 10 mV/g for acceleration and 100 mV/in/s for velocity, both ±5%, measured at 100 Hz with a 10 kΩ load. Acceleration range is 500 g with ±1% amplitude linearity, velocity range is 50 in/s, and the two channels do not share the same frequency response, which matters when the same machine is protected on velocity and diagnosed on acceleration.

Parameter Velocity output Acceleration output
Sensitivity 3.94 mV/mm/s (100 mV/in/s) ±5% 1.02 mV/m/s² (10 mV/g) ±5%
Full-scale range 1,270 mm/s (50 in/s) 4,900 m/s² (500 g)
Frequency response, ±5% 40 Hz to 1 kHz (2,400–60,000 cpm) 25 Hz to 4 kHz (1,500–240,000 cpm)
Frequency response, ±3 dB 25 Hz to 2 kHz (1,500–120,000 cpm) 10 Hz to 10 kHz (600–600,000 cpm)
Broadband noise floor, 5 Hz to 2 kHz 0.05 mm/s rms max 147 mm/s² (1.5 mg) rms max
Output bias −10.0 ± 2.0 Vdc −10.0 ± 2.0 Vdc
Deviation at +399 °C sensor ±10% of nominal ±10% of nominal
Deviation at +482 °C sensor ±15% of nominal ±15% of nominal

All of these figures are stated with 305 m (1,000 ft) of cable, so the frequency response already includes the cable effect at the maximum permitted length. The other electrical limits are a maximum cable length of 305 m, transverse sensitivity below 5% of axial, mounted resonance above 15 kHz, and a case-isolated output that allows the electronics to be grounded independently of the machine.

What cable, connector and installation limits apply?

The integral cable is a 300-series stainless steel mineral-insulated cable with a stainless steel overbraid, 6.35 ± 1.27 mm in diameter, with a 51 mm minimum bend radius. It is permanently attached at both ends, which is the point of the design: no connector sits in the hot zone. The only connector is the MIL-DTL-83723/90-1006N at the electronics, and the only user-selected cable is the separate 350901 field interconnect.

The mineral-insulated construction is what makes the 482 °C cable rating credible. A conventional FEP-insulated transducer cable is limited to roughly 177 °C, which is why high-temperature accelerometer installations normally stop at the probe and put the cable in a heat-protected route. Here the cable is part of the hot-zone assembly, so the heat-protected route starts at the electronics housing instead.

Ordering is by cable length in inches: 023, 026, 027, 044, 077, 083, 158, 237, 315 and 394, covering 0.58 m to 10.0 m. The 350901 field cable adds 10 ft (3.05 m) or 40 ft (12.2 m). The 305 m maximum applies to the total cable run, not to the integral cable alone, so a long field-cable route consumes the same budget as a long integral cable. System weight is 0.545 kg plus 0.10 kg per metre of cable, which is worth checking on a thin casing or a long cantilever bracket.

Is the 350900 approved for hazardous areas, and what powers it?

The 350900 carries genuine hazardous-area approvals, and they are the reason the supply range narrows to −18 to −28 Vdc. ATEX/IECEx lists II 1 G Ex ia IIC or IIB and II 3 G Ex ec, and the North American listing covers Class I Div 1 and Div 2 with a T4/T1 temperature class split at 492 °C. The sensor must be powered from a limited-energy circuit or a Class 2 supply; it does not need an external charge amplifier, because the electronics are integral.

Item Published value
Supply voltage, general purpose −18 to −30 Vdc
Supply voltage, hazardous area −18 to −28 Vdc
Quiescent current 6 mA nominal, no load
ATEX/IECEx marking II 1 G Ex ia IIC or IIB; II 3 G Ex ec IIC or IIB
North American marking Class I, Zone 0, AEx ia IIC/IIB; Class I, Div. 1 and Div. 2, Groups A–D
Entity parameters, IIC Ui 28 V, Ii 153 mA, Pi 0.84 W, Ci 37 nF, Li 30 µH
Entity parameters, IIB Ui 29.2 V, Ii 279 mA, Pi 1.95 W, Ci 37 nF, Li 30 µH
Temperature class T4: −40 °C to +100 °C (electronics); T1: −40 °C to +482 °C (sensor and cable)
Installation drawing 167923

The T4/T1 split is the clearest statement in the document that the hot zone and the electronics zone are different environments. T4 is the electronics housing at 100 °C; T1 is the sensor and cable at 482 °C. Anyone specifying this sensor for a Zone 0 or Division 1 location should read drawing 167923 together with the entity parameters, because the barrier selection is driven by Ui, Ii and Pi rather than by the nominal 24 V supply.

How does the 350900 compare with other Bently Nevada vibration sensors?

It is the only sensor in the line that combines a 482 °C sensing head with simultaneous velocity and acceleration outputs. A standard accelerometer stops far below that temperature, a piezo-velocity sensor such as the 330505 covers low frequencies but not acceleration diagnostics, and a 3300 XL proximity system measures shaft-relative motion rather than casing vibration, so the three are complementary rather than interchangeable.

Approach What it measures High-temperature limit Outputs Typical role
350900 HTVAS Casing vibration +482 °C (head and MI cable) Velocity and acceleration, simultaneous Hot casing protection plus diagnostics
330505 low-frequency velocity sensor Casing velocity Standard industrial range, not 482 °C Velocity Low-frequency casing protection
3300 XL 8 mm proximity system Shaft position and vibration Probe dependent, 177 °C standard, 218 °C ETR Displacement, plus Keyphasor and speed Fluid-film bearing machines
Standard IEPE accelerometer Casing acceleration Typically well below 482 °C Acceleration General machinery diagnostics

The comparison matters when a specification asks for “vibration protection” without saying what is being measured. On a machine with fluid-film bearings, the protection measurement is usually shaft displacement from a 3300 XL 8 mm probe, and the casing measurement is a separate decision. On a rolling-element or casing-critical machine, the 350900 is doing the protection job itself, and its acceleration channel is the diagnostic channel rather than a second protection channel.

Which monitor channels and spares should you plan for?

Budget two monitor channels per sensor, not one. The acceleration and velocity outputs must land on a separate channel pair of a 3500/42M or 3500/44M, so a machine with four 350900 sensors consumes eight channels. The rest of the bill of materials is the 350901 field cable, a limited-energy supply, and the rack items that already exist in a 3500 installation.

On the monitor side, the 3500/42M Proximitor and seismic monitor is the usual destination for both channels. Power comes from the rack, and a 3500/15 universal AC supply or the 129486-01 high-voltage DC version covers the rack side, with the limited-energy requirement applying at the sensor circuit rather than at the rack. Local status reading still goes through a 3500/94M rack display, and the rack-to-System 1 path is covered in our note on the 3500/22M Transient Data Interface.

Three spares are worth holding. The 350901 field interconnect cable is the item that stops a restart because it is length-specific and not stocked locally. A spare 200151 accelerometer cable covers the conventional accelerometer channels on the same machine, and a 330450-60 MIL-C-5015 connector is the usual field repair part for those channels. For the velocity-only channels elsewhere on the train, the 330505 low-frequency velocity sensor is the like-for-like alternative.

If the same machine also needs shaft-relative measurement, the other half of the chain is the 3300 XL 8 mm displacement system: a probe, an extension cable and a Proximitor Sensor. The 330380-91-00 9 m DIN Proximitor Sensor is the DIN-rail signal conditioner for that system, and it is the natural companion to this casing sensor on a turbine train.

What is not published?

  • No 482 °C rating for the electronics housing or the connector. The published electronics limit is +125 °C, and the ATEX ambient limit for the housing is +100 °C.
  • No separate velocity integrator or charge amplifier in the ordering matrix. The 350900-AAA order code selects cable length only.
  • No gas-turbine-stage-specific application statement. The datasheet describes high-temperature casing measurement and instructs installation on the bearing housing or machine casing; it does not name combustor or turbine stages as a qualified location.
  • No sensitivity other than 10 mV/g and 100 mV/in/s. There is no 100 mV/g acceleration option in this datasheet.
  • No cable material option. The integral cable is 300-series stainless mineral-insulated with stainless overbraid; there is no FEP or PFA variant listed.
  • No statement that the electronics can be separated from the sensing head in the field. The datasheet describes them as permanently connected by a hardline cable.
  • No published lifetime or drift figure beyond the ±10% and ±15% sensitivity bands over temperature.

Frequently asked questions

Is the Bently Nevada 350900 rated to 482 °C at the probe only?

No. The datasheet rates both the sensing head and the mineral-insulated integral cable to −54 °C to +482 °C. The integral signal-conditioning electronics are rated to −54 °C to +125 °C, with a four-hour survival exposure at +155 °C during which electrical performance is not guaranteed. In a hazardous area the electronics housing ambient limit is +100 °C for T4.

Does the 350900 produce velocity and acceleration at the same time?

Yes. The datasheet describes a continuous acceleration and velocity output from one sensing head, with the velocity signal generated by the integral electronics rather than by an external integrator. Both outputs are available simultaneously, but they must be wired to a separate channel pair on a 3500/42M or 3500/44M monitor, or to separate monitors.

What are the acceleration and velocity sensitivities of the 350900?

Acceleration is 1.02 mV/m/s² (10 mV/g) ±5%, and velocity is 3.94 mV/mm/s (100 mV/in/s) ±5%, both specified at 100 Hz with a 10 kΩ load and 305 m of cable. The datasheet offers no 100 mV/g acceleration variant.

Does the 350900 need an external charge amplifier?

No. The signal-conditioning electronics are integral and permanently connected to the sensing head, and the assembly is powered from −18 to −30 Vdc at 6 mA nominal. What it needs is a limited-energy or Class 2 supply, and in a hazardous area a barrier selected against the published entity parameters.

How many monitor channels does one 350900 use?

Two. The acceleration and velocity signals must go to a separate channel pair, such as channels 1 and 3 on the same monitor, or to separate monitors. A single channel pair cannot carry both measurement types, so a four-sensor installation needs eight channels.

How long can the 350900 cable run be?

305 m (1,000 ft) maximum in total. The integral cable is ordered in lengths from 0.58 m to 10.0 m using the 350900-AAA code, and the separate 350901 field interconnect cable adds 10 ft or 40 ft. Every published frequency-response figure assumes the full 305 m, so shorter runs do not invalidate them.

What is the 350900 cable made of, and can it be replaced in the field?

The integral cable is a 300-series stainless steel mineral-insulated cable with a stainless steel overbraid, 6.35 ± 1.27 mm diameter and a 51 mm minimum bend radius. It is permanently connected to the sensing head and the electronics, so it is not a field-replaceable item. The field interconnect cable, 350901, is the replaceable segment.

Is the 350900 intrinsically safe?

It has intrinsically safe approvals. ATEX/IECEx lists II 1 G Ex ia IIC or IIB for Zone 0/1 and II 3 G Ex ec for Zone 2, and the North American listing includes Class I, Zone 0, AEx ia and Class I, Div. 1 and Div. 2. Safe use requires connection to a compatible associated apparatus and compliance with installation drawing 167923.

What is the difference between the 350900 and a 3300 XL proximity probe?

The 350900 is a casing-mounted velocity and acceleration sensor for high surface temperatures. A 3300 XL 8 mm probe is an eddy-current displacement sensor that measures shaft motion relative to the bearing, with a standard probe limit of 177 °C and an ETR probe limit of 218 °C. They answer different questions and are often used together on the same machine train.

Can the 350900 be used on a gas turbine casing?

The datasheet supports high-temperature casing measurement up to +482 °C and requires mounting on the bearing housing or machine casing, but it does not list combustion or turbine stages as qualified locations. Treat stage-level installation as an engineering review with Bently Nevada rather than a catalogue application, and confirm the local ambient at the electronics housing stays below its rating.

Sources

Every figure above was read from Bently Nevada datasheet 168780 Rev. L on 11 November 2026. Where the source material described the whole assembly as rated to 482 °C, this article states the split between the sensor and cable (+482 °C) and the electronics (+125 °C, +100 °C ambient in a hazardous area). Where the source material implied the velocity output required separate signal conditioning, this article states that both outputs come from the integral electronics. Items the datasheet does not publish are listed as unpublished rather than estimated.