Bently Nevada 3500/22M TDI: 100Base-FX, Not Gigabit Ethernet

Engineer reviewing machine condition data on a screen beside a machining centre

The Bently Nevada 3500/22M Transient Data Interface connects a 3500 rack to System 1 over 100 Mbit/s Ethernet — 100Base-FX multimode fiber or 10/100Base-TX copper. It is not a gigabit link, and the datasheet offers no gigabit option. The module is also not part of the protection path: Bently Nevada states that it “is not part of the critical monitoring path” and has no effect on automatic machinery protection. The “zero packet loss” and “enhanced model” claims that circulate with this module are not in the Bently Nevada documentation.

TL;DR

  • Physical layer: 100Base-FX fiber (full duplex multimode, IEEE 802.3u, MT-RJ connector, 2,000 m maximum) or 10Base-T/100Base-TX copper (RJ-45, 100 m maximum). There is no 1000Base-X or gigabit interface on the TDI.
  • “Single cable to System 1” is accurate; “gigabit” is not. Bently Nevada’s own product page describes using the Ethernet port and a single network cable, and the manual says the TDI behaves as a standard network device, so a direct run to the System 1 server is possible. The line rate is still 100 Mbit/s.
  • No official “enhanced” version. The ordering matrix defines one TDI type, 01 Standard. A TMR version exists (spare 288055-02, order type 02 in the original manual), and the “M” in 3500/22M marks the M-series generation, not an enhanced feature set.
  • “Zero packet loss” is not a Bently Nevada claim. The manual describes store-and-forward behaviour: if the TDI cannot send, it stores the data and sends it later. It also warns that the module’s memory will eventually fill if the host cannot keep up, and states a transfer rate of about one waveform set per second per DAQ.
  • Protection is unaffected. Trip decisions are made by the monitor modules and executed through relay modules (3500/32, 3500/33, 3500/34). The TDI’s OK relay reports rack OK status; it is not a trip output.
  • Four Keyphasor inputs, 48 dynamic channels, 2,048 samples per waveform. Speed range narrows as channels are enabled: 100,000 rpm for 1–16 channels, 60,000 rpm for 17–24, 30,000 rpm for 25–48.
  • Not the same product as the 3500/92. The TDI carries waveforms and transient data to System 1; the 3500/92 exposes current values and statuses to a DCS or PLC over Modbus.

What is the 3500/22M and where does it sit in the rack?

The 3500/22M is the rack interface and data collector in one module. It performs the functions of the older 3500/20 Rack Interface Module and adds the data collection role that used to sit in an external communication processor such as TDXnet. Every 3500 rack needs one TDI or one RIM, and it always occupies Slot 1, next to the power supplies.

Physically it is a two-part assembly: a front module in a full-height front slot, and an I/O module in the corresponding full-height rear slot. The I/O module is where the Ethernet port lives, which is why the copper and fiber versions are separate order codes. The front module carries the key switch, the rack address switch, status LEDs, a USB-B configuration port, the rack reset button and the OK relay connections.

Item Published value
Function Rack interface plus data collector for System 1 and 3500 configuration software
Rack position Slot 1, adjacent to the power supplies; one TDI or RIM per rack
Rack slots used 1 full-height front slot + 1 full-height rear slot (I/O module)
Power consumption 10.5 W
Dynamic channels Up to 48, across up to 12 M-series monitors
Keyphasor inputs Four 3500 system Keyphasor signals
Waveform length 2,048 samples per channel, 16-bit, synchronous and asynchronous
Rack addresses 127
Operating temperature −30 °C to +65 °C
Humidity 95%, non-condensing
Mass 0.91 kg module, 0.20 kg I/O module
Battery life 38 years powered at 50 °C; 12 years unpowered

The module has no measurement inputs of its own. It reads data across the rack backplane from the monitor modules — for example a 3500/42M Proximitor and seismic monitor for shaft and casing vibration, a 3500/50M tachometer for speed, or a 3500/61 temperature monitor for bearing and winding temperatures. That separation is the reason the TDI can fail without taking protection with it.

Does the 3500/22M use gigabit Ethernet or 100Base-FX fiber?

It is 100 Mbit/s, in both variants. The datasheet lists two Ethernet I/O options and neither is gigabit:

Interface Standard Connector Maximum distance Order code
10Base-T / 100Base-TX copper IEEE 802.3, autosensing RJ-45 100 m (328 ft) 146031-01
100Base-FX fiber IEEE 802.3u, full duplex multimode MT-RJ male on the module 2,000 m (6,560 ft) 146031-02

Both versions carry the same two protocols over TCP/IP: the BN Host Protocol, used by the 3500 configuration and data acquisition software, and the BN TDI Protocol, used by System 1. Nothing in the datasheet, the ordering matrix or the operation and maintenance manual mentions 1000Base-T, 1000Base-SX or any gigabit variant.

Where does the “gigabit” description come from?

Most likely from a reasonable but wrong inference: a modern server NIC is gigabit, a fiber link sounds fast, and the marketing phrase “single network cable” reads like a direct high-speed pipe. Bently Nevada’s own product page says only that you can “use the Ethernet port in the 3500/22M Transient Data Interface Module and a single network cable to communicate with our System 1 software”. It does not state a speed, and the datasheet states 100 Mbit/s.

For this application the difference rarely matters, and that is worth understanding rather than just correcting. A 48-channel waveform set is 48 × 2,048 samples × 2 bytes, about 196 kB before protocol overhead. At the documented transfer rate of one waveform set per second, that is roughly 1.6 Mbit/s of payload — about 1.6% of a 100 Mbit/s link. Gigabit would buy nothing; the constraint is the data management architecture behind the port, not the wire.

Do you need a switch or hub?

Not necessarily. The manual states that the TDI “is designed to work as a standard network device and should be compatible with any Ethernet structure”. A single rack can therefore be connected directly to the System 1 server, or through a managed switch alongside other racks. What the documentation does insist on is grounding discipline: the I/O module has a two-pin connector for tying Signal Common to a single-point instrument ground, and if you use it, the selector on the power input module must be moved to the HP position to isolate signal common from chassis ground. The front USB port is a separate trap — the specific 123M4610 cable is required to preserve chassis-to-ground isolation, and the attached computer must run on battery to avoid a ground loop.

Which fiber and connector do you actually need?

The module has an MT-RJ male connector, so the cable must be terminated MT-RJ female. Bently Nevada’s fiber cable option (161756-AAA) is 100Base-FX multimode with MT-RJ female connectors in standard lengths up to 1,300 ft (400 m). The interface itself supports 2,000 m, so the cable catalogue, not the transceiver, is the practical limit for most orders. If the run already exists as ST or LC patch panels, plan for MT-RJ-to-ST or MT-RJ-to-LC adaptation and count the extra connectors in the loss budget.

For copper, the specified cable is shielded Category 5 with RJ-45 connectors (138131-AAA), in lengths up to 320 ft. In a plant with VFD-driven motors, the shield and the single-point ground are not optional details; they are the difference between a link that stays up and one that drops during a drive start.

Engineer reviewing machine data on a laptop beside a machining centre with HMI screens
Condition data is only useful if it reaches the host reliably. The TDI is the rack-side endpoint of that path. Image for illustration, not Bently Nevada equipment.

Is there an “enhanced” 3500/22M, and how does it differ from the standard TDI?

There is no enhanced TDI type in the Bently Nevada documentation. The ordering matrix has a single entry for the interface type:

Order position Option Meaning
A — TDI type 01 Standard, for standard monitoring applications
B — I/O type 01 / 02 / 03 / 04 Copper / fiber / copper with gold-plated OK relay / fiber with gold-plated OK relay
C — approval 00 / 01 / 02 None / CSA NRTL-C Class I Div 2 / Multi (CSA, ATEX, IECEx)

So a standard module is ordered as 3500/22-01-01-00 (copper) or 3500/22-01-02-00 (fiber), and the spares list carries one module part number: 288055-01. Any channel or Keyphasor difference you read about between “standard” and “enhanced” is not a documented distinction, because there is no second type to compare against.

Two things do exist and are easy to confuse with an “enhanced” model:

  • A TMR version. The original operation and maintenance manual lists interface type 02 TMR alongside 01 Standard, and the TMR module appears in spares lists as 288055-02. That is a redundancy option for triplicated architectures, not a faster or higher-channel TDI.
  • The “M” in the model name. 3500/22M denotes the M-series generation, which replaced the earlier 3500/22. Resellers sometimes render that generational change as “enhanced”, and a few listings attach the label to 146031-01, which is the copper I/O module rather than the TDI. Neither usage is a Bently Nevada designation.

How many Keyphasor and speed inputs does it have?

Four. The TDI accepts one to four speed signals identical to those available elsewhere in the 3500 system, and uses them for synchronous waveform sampling, nX amplitude and phase values, and transient triggering. It supports once-per-revolution Keyphasor signals, multiple-event-per-revolution signals up to 20 kHz, and the Recip Multi-Event Wheel configuration. When a multiple-event signal is used, the TDI marks all phase-related data as invalid — a detail worth knowing before you promise orbit plots from a gear-tooth reference.

Channel count and speed range are linked, because the rack has finite sampling capacity:

Dynamic channels enabled Minimum speed Maximum speed
1 to 16 1 rpm 100,000 rpm
17 to 24 1 rpm 60,000 rpm
25 to 48 1 rpm 30,000 rpm

Which slot limits apply?

The TDI itself must be in Slot 1 and needs a matching rear slot for its I/O module; that is the only slot restriction the documentation places on it. The channel count is not limited by slots but by the optional 3500/09-AAA-BBB Dynamic Data Enabling Disk, which licenses steady-state points (000–672) and transient points (002–672) with the two fields summing to 672 or less. One disk can serve multiple TDIs. Without a disk, static data capture is standard but waveform and high-resolution transient capture are not enabled.

What data does the TDI collect, and can it guarantee zero data loss?

Three modes, each with published characteristics:

Mode What is captured Published detail
Current values Static values from every monitor in the rack Four nX amplitude and phase values per point
Alarm data Pre- and post-event static and waveform data 10 min of 1 s static before and 1 min after; 20 s of 100 ms static before and 10 s after; 2.5 min of 10 s waveforms before and 1 min after
Transient data Startup and coastdown data at programmed speed or time increments Two programmable speed windows for initiation; independent increasing and decreasing speed intervals

Now the part that matters for procurement language. The manual does not promise lossless transfer. It describes a store-and-forward design and states the limits plainly:

  • “TDI attempts to move data to the host computer at the earliest opportunity… If TDI is unable to send the data it will store the data and send it when it is able to do so.”
  • “TDI can collect a large amount of data in a short time and unless the system can handle transferring it to the software the TDI’s memory will eventually fill up.”
  • “System 1 / TDI can transfer a waveform set at a rate of 1 set per second. If 2 TDIs are connected to a single DAQ and both TDIs are in transient mode then the computer takes 2 seconds to collect a waveform set.”
  • In addition to alarm and pre-transient storage, the TDI holds 35 waveform sets internally.

That is a buffer, not a guarantee. TCP/IP will retransmit lost packets at the transport layer, and the internal buffer absorbs short interruptions, but a sustained mismatch between collection rate and transfer rate ends in overwritten data. The honest specification for a tender document is not “zero packet loss”; it is a statement of the collection rate you intend to use, the transfer rate available, and the buffer depth that covers your worst-case outage.

How does transient collection work on a turbine?

Transient mode is initiated when a collection point enters a configured speed window, or manually from the host. Inside the window, the TDI collects a full static set for the collection group at every collection event and a waveform set every ten events, so a mix of speed-based and time-based events both contribute. Data already captured before the trigger is kept: 200 static sets and 20 waveform sets of pre-transient history.

The recording interval is set by Delta RPM for speed-based buffers or Delta Time for time-based buffers, and the manual gives the sizing rule:

Delta RPM ≥ [(Maximum Speed − Minimum Speed) / (35 + Ramp Time / Transfer Rate)] / 10

For a machine ramping from 100 rpm to 15,000 rpm in two minutes with three TDIs on one DAQ, the worked example lands at 19.8 rpm, producing about 752 static sets and 75 waveform sets during the event. This is the arithmetic that makes a startup record usable — too fine an increment and the buffer overruns during the ramp; too coarse and the critical speed band is captured in two or three points. Note also the caveat in the manual: after a TDI reconfiguration, or immediately after startup, the historical buffer may not be full and a partial pre-event record is returned.

Does the TDI affect machinery protection or trip logic?

No, and this is stated more clearly in the Bently Nevada documents than almost anything else about the module.

The datasheet: “Although the TDI provides certain functions common to the entire rack, it is not part of the critical monitoring path and has no effect on the proper, normal operation of the overall monitor system for automatic machinery protection.” The manual repeats it: “The TDI’s operation (or non-operation) has no effect on the proper, normal operation of the overall monitoring system.”

The architecture explains why. Measurement and voting happen in the monitor modules. Trip decisions are executed by the rack’s relay modules — the 3500/33 16-channel relay module, the 3500/32 four-channel relay module, or the 3500/34 TMR relay module — which are wired to the machine’s trip system independently of the data path. The TDI reads from the backplane and writes to Ethernet. Remove it and the rack keeps measuring, alarming and tripping; you lose the data, not the protection.

One relay on the TDI is worth understanding, because it is routinely mistaken for a trip contact. The OK relay on the I/O module annunciates the OK or NOT OK status of the overall rack, and it is normally energised. It is an annunciation output, not a protection output, and it is not part of the trip matrix. The same I/O module also carries the dry contacts for Trip Multiply, Alarm Inhibit and Rack Reset, all of which are control inputs with less than 1 mA of current.

Practical consequence for maintenance: you can replace a TDI, pull its I/O module or reboot the data path while the machine runs, provided the rack stays powered and the monitor modules are undisturbed. What you cannot do is leave the old RIM I/O in the rack during an upgrade — the datasheet warns explicitly that doing so will damage the TDI, and prescribes the order: remove RIM, remove RIM I/O, insert TDI I/O, insert TDI.

How does the 3500/22M differ from the 3500/92 communication gateway?

They solve different problems and are often both present in the same rack.

Item 3500/22M TDI 3500/92 Communication Gateway
Primary role Rack interface and data collector for System 1 Modbus gateway to a DCS, PLC or historian
Data carried Static values, alarm data, waveforms and transient records Current measured values, module statuses and current alarm statuses
Protocols BN Host Protocol and BN TDI Protocol over TCP/IP Modbus RTU over RS-232/422/485, Modbus/TCP, and the BN host protocol
Physical layer 100Base-FX fiber or 10/100Base-TX copper 10BASE-T Ethernet (RJ-45, star topology) and serial
Rack position Slot 1 Its own module slot, in addition to the TDI
Power 10.5 W 5.0 W typical (RS-232/422), 5.6 W typical (RS-485)
Update rate Event-driven, up to one waveform set per second Data collection not exceeding 1 second for all modules in the rack

Read the “data carried” row carefully, because it is where integration projects go wrong. The 3500/92 is a register-mapped view of current values and statuses. It is the right module when the customer’s DCS needs vibration magnitudes and alarms in Modbus, and it is the wrong module when the requirement is a coastdown Bode plot or an orbit at the moment of trip. Waveforms and transient records come from the TDI into System 1. If a specification asks for both, the rack needs both modules, and the network design has to carry both.

Which order codes and spares should you specify?

Use the full 3500/22-AA-BB-CC string, because “3500/22M” alone does not define the interface. The most common field error is ordering a fiber system with a copper I/O module, or the reverse, and discovering it at commissioning.

Part number Description
3500/22-01-01-00 Standard TDI with 10Base-T/100Base-TX copper I/O, no agency approval
3500/22-01-02-00 Standard TDI with 100Base-FX fiber I/O, no agency approval
288055-01 Standard TDI module, supplied with USB cable
288055-02 TMR TDI module
146031-01 10Base-T/100Base-TX I/O module
146031-02 100Base-FX fiber optic I/O module
161580 TDI operation and maintenance guide
123M4610 10 ft USB A-to-B cable, required for ground isolation
138131-AAA Shielded Category 5 Ethernet cable, RJ-45, 6–320 ft
161756-AAA 100Base-FX fiber cable, MT-RJ female, 10–1,300 ft
3500/09-AAA-BBB Dynamic Data Enabling Disk, steady-state plus transient points ≤672

Two supporting items are worth holding as spares rather than ordering at failure: the I/O module, because it carries the only Ethernet port and the OK relay, and the correct USB cable, because a generic cable defeats the isolation design. Rack power is the other common single point — a 3500/15 universal AC power supply or the 129486-01 high-voltage DC version depending on the substation. For the sensor side, the CB2W100-15 interconnect cable is the kind of line item that stops a restart, and the 3500/94M rack-mount display is still the fastest way to read rack status locally when the network is the thing being repaired.

For the commercial side of these buys, our notes on sourcing a Bently Nevada power module without overpaying and on 2026 automation lead times describe what the current market looks like. If you are still building the business case for the monitoring layer itself, why condition monitoring pays for itself in a year covers the payback arithmetic.

What is not published?

  • No gigabit interface, in any revision of the datasheet or in the ordering matrix.
  • No official “enhanced” TDI type. Only Standard (01) and the TMR variant appear in Bently Nevada documentation.
  • No “zero packet loss” or lossless-transfer specification. The manual describes buffering and warns that memory can fill.
  • No statement that the TDI is in, or can be placed in, the protection path. The documentation says the opposite.
  • No published end-to-end latency figure for alarm data reaching System 1, and no guaranteed delivery time.
  • No transient record length in seconds. The limit is expressed as a buffer of 35 waveform sets plus the Delta RPM or Delta Time rule, not as a fixed recording duration.
  • No fieldbus option. Profibus, Profinet, EtherNet/IP and OPC UA are not native to the TDI; integration to a control system goes through the 3500/92 or through System 1.

Frequently asked questions

Is the Bently Nevada 3500/22M gigabit Ethernet?

No. The TDI provides 10Base-T/100Base-TX copper or 100Base-FX multimode fiber, both at a maximum of 100 Mbit/s. The datasheet conforms the fiber port to IEEE 802.3u and lists no gigabit option.

What fiber connector and distance does the 3500/22M support?

The module has an MT-RJ male connector, so the cable must be MT-RJ female. The 100Base-FX interface supports multimode fiber runs up to 2,000 m, while Bently Nevada’s own fiber cable option is catalogued in lengths up to 1,300 ft (400 m).

Is there an enhanced version of the 3500/22M?

There is no enhanced TDI type in the Bently Nevada ordering matrix, which lists only type 01 Standard. A TMR variant exists as spare 288055-02. The “M” denotes the M-series generation that replaced the earlier 3500/22, and some resellers describe that generational change as “enhanced”.

How many Keyphasor inputs does the TDI have?

Four. It accepts one to four speed signals, supports once-per-revolution Keyphasor, multiple-event-per-revolution up to 20 kHz, and the Recip Multi-Event Wheel. Maximum speed depends on how many dynamic channels are enabled: 100,000 rpm up to 16 channels, 60,000 rpm up to 24, and 30,000 rpm up to 48.

Does the TDI lose data if the network goes down?

It buffers. The manual states that if the TDI cannot send data it stores it and sends when it can, and that the module holds 35 waveform sets in addition to alarm and pre-transient storage. That is not a guarantee of lossless capture: the manual also warns the memory will eventually fill if the host cannot keep up with the collection rate.

Does removing or failing the TDI trip the machine?

No. Bently Nevada states that the TDI is not part of the critical monitoring path and that its operation or non-operation has no effect on automatic machinery protection. Trip decisions are made by the monitor modules and executed through the rack relay modules.

Is the TDI’s OK relay a trip contact?

No. The OK relay on the I/O module annunciates the OK or NOT OK status of the whole rack and is normally energised. It is an annunciation output, separate from the trip relay matrix built on the 3500/32, 3500/33 and 3500/34 modules.

What is the difference between the 3500/22M and the 3500/92?

The 3500/22M collects static, alarm, waveform and transient data for System 1 over Ethernet. The 3500/92 is a Modbus gateway that exposes current values, module statuses and current alarms to a DCS or PLC over Modbus RTU or Modbus/TCP. A rack that needs both waveform analysis and Modbus integration uses both modules.

Can I connect the TDI directly to the System 1 server without a switch?

Yes. The manual describes the TDI as a standard network device compatible with any Ethernet structure, and Bently Nevada’s product page refers to a single network cable to System 1. Direct connection and switched connection are both valid; the copper limit is 100 m and the fiber limit is 2,000 m.

Can the 3500/22M record turbine startup and coastdown transients?

Yes, provided a Dynamic Data Enabling Disk licenses transient points. Collection starts when machine speed enters one of two programmable windows, at increments set by Delta RPM or Delta Time, and keeps 200 static sets and 20 waveform sets of pre-trigger history.

Which spare part numbers should be kept on site for a 3500/22M?

The module is 288055-01 (or 288055-02 for TMR), the I/O module is 146031-01 for copper or 146031-02 for fiber, the guide is 161580, and the isolation-safe USB cable is 123M4610. The I/O module is the item that carries the only Ethernet port, so it is the one worth stocking.

Sources

All specifications above were read from the Bently Nevada datasheet (161581) and the 3500/22M operation and maintenance manual (161580) on 10 November 2026. Figures that the documents do not publish are listed as unpublished rather than estimated; the 196 kB waveform-set size is arithmetic from the published 48-channel and 2,048-sample figures and excludes protocol overhead.